4 Way Switch Circuits
2011 NEC Compliant
Power Source 3rd switch, Fixture Feed 2nd switch
(2011 NEC new rule 404.2 (C) Compliant)
For more information on this new rule read
‘2011 NEC New Rule ‘Switch Connections’
You will need…
- A 4 wire cable that is routed between switch box 1 and switch box 2 – these wire cables comes with a black / red / blue (or white striped) / white wire plus the bare equipment grounding wire.
- A 3 wire cable that is routed between switch box 2 and switch box 3 – these wire cables comes with a black / red / white wire plus the bare equipment grounding wire.
- A 2 wire cable that is routed between switch box 2 and the fixture box – this wire cable comes with a black / white wire plus the bare equipment grounding wire.
- A circuit power supply source wire cable that is routed to switch 3.
- Insulated wire nuts to connect / join wire together, variety of sizes out there so make sure you obtain the correct size.
- Wire staples, to affix the wire cables to wall studs as needed. Wire cable must be secured within 6 inches of entering the electrical box.
- Wire cable / wire strippers.
- Screwdrivers as required.
Holes drilled to feed wires through studs must be 1 1/4″ from edge of stud, in instances where the wire cable is closer then the edge of stud must have a 1/16-in. thick protective metal plate over the area where the cable is being feed through (may want to notch the stud so that that the protective plate does not create a bump on the drywall). Also read the article called ‘Wire Routing Basics’
Wire cables entering the electrical box – secure the cable clamp at the box snug enough that the cable cannot come out but not too tight as to pinch the cable and break through the insulated cover of the cable.
You must have at least 6 inch length of wire inside the electrical box, it can be a bit more but not less, it can fail an inspection if the length of each wire is less than 6 inches. Also read the article called ‘Box Fill Calculations’ as there is a limit on how many wires are allowed for a certain size electrical box.
STEP 1 – Make certain that the power supply cable is dead – turn off the electrical breaker at the service panel. Make certain that everyone in the house is aware of what you are doing so that they do not get the notion to reset the breaker when another light in the home is not working.
STEP 2 – Make the box openings (if a existing home)
STEP 3 – Feed / Route the wire cables.
STEP 4 – Mount / Install the Electrical Boxes (make sure the electrical boxes are secured as some fixtures are heavy and may require additional support) [The electrical box should not extend beyond the edge of the finished wall or ceiling so that the fixture can mount flush to the ceiling and the wall switch cover will mount flush – but it also should not be recessed too far into the wall or ceiling]; then feed the wire cables into the electrical boxes. Sometimes because of tight openings in existing homes, the wire cable may to be feed into the electrical box then the box put in position and secured.
STEP 5 – Connect the wires…
Connections Instructions:
(as depicted in the diagrams above)
At the Fixture box…
One cable entering this box, going coming from switch 2.
- a) connect the black wire coming from switch 2 to the switched ungrounded conductor (hot) of fixture (shown as black in picture) – if the fixture has screw type connections then connect to brass color screw.
- b) connect the white wire coming from switch 2 to the grounded conductor (neutral) of fixture (shown as white in picture) – if the fixture has screw type connections then connect to the silver color screw.
- c) please see under important notes in regards to the equipment grounding conductor (bare wire).
At switch 1 box…
One cable entering this box coming from switch 2.
- a) connect the black wire coming from switch 2 to the common screw of switch 1.
- b) connect the red wire coming from switch 2 to the one of the remaining main screws of switch 1.
- c) connect the blue wire coming from switch 2 to the last remaining main screw of switch 1.
- d) using an insulated wire nut cap off the white wire.
- d) please see under important notes in regards to the equipment grounding conductor (bare wire).
At switch 2 box…
Three cables entering this box, one coming from fixture, one cable from switch 1 and one cable from switch 3.
- a) using an insulated wire nut connect / join the white wire coming from fixture + the white wire coming from switch 3 + the white wire coming from switch 1.
- b) using an insulated wire nut connect / join the black wire coming from fixture + the black wire coming from switch 1.
- c) connect the red wire coming from switch 1 to the one screw that is a matching pair of screws on switch 2 (both the red and blue wires coming from switch 1 must go to a matching pair of screws at switch 2)
- d) connect the blue wire coming from switch 1 to the 2nd screw that is a matching pair of screws on switch 2 (both the red and blue wires coming from switch 1 must go to a matching pair of screws at switch 2)
- e) connect the red wire coming from switch 3 to one screw from a different matching pair of screws. (both the red and black wires coming from switch 3 must go to a matching pair of screws at switch 2)
- f) connect the black wire coming from switch 3 to the 2nd screw that is a matching pair. (both the red and black wires coming from switch 3 must go to a matching pair of screws at switch 2)
Just to clarify further – The red and blue wires coming from switch 1 go to one set of matching screws at switch 2 — The red and black wires coming from switch 3 go to a different set of matching screws at switch 2 – A matching set is 2 screws of the same color.
- g) please see under important notes in regards to the equipment grounding conductor (bare wire).
At switch 3 box…
Two cable entering this box, one cable coming from switch 2, and one cable coming from ‘circuit power supply cable’
- a) connect the black wire coming from ‘circuit power supply cable’ to the common screw of switch 3.
- b) using an insulated wire nut connect / join the white wire coming from ‘circuit power supply cable’ + the white wire coming from switch 2.
- c) connect the red wire coming from switch 2 to one of the remaining main screws of switch 3.
- d) connect the black wire coming from switch 2 to the last remaining main screw of switch 3.
- e) please see under important notes in regards to the equipment grounding conductor (bare wire).
Important Notes:
By electrical codes you MUST have at least 6 inches of wire in the electrical box itself, and also the wire must be able to reach at least 3 inches outside the box, it can fail an electrical inspection if the required min. wire length is not met. You may have the wires a bit longer (within reason) but they cannot be shorter. Also see the note on box fill further down in this article.
If the fixture has screw type connectors, the ungrounded conductor (hot) is connected to the brass color screw, and the grounded conductor (neutral) is connected to the silver color screw. If it has black and white wires coming from fixture, then just connect black to black and white to white. Use wire nuts of the correct size to join wires together.
The wire cable running between switch 1 & switch 2 has 4 wires in it – black / red / blue / white (plus the bare equipment grounding wire). The wire cable between switch 2 and 3 has 3 wires in it – black / red / white (plus the bare equipment grounding wire).
What is not shown in the drawings to avoid confusion, is that each wire cable also has a bare equipment grounding wire included. This wire is connected to a grounding screw in each electrical box (if the box is metal), joined either through the grounding screws in the box itself or via a wire nut to the bare wire of the next cable entering / exiting the box, it is also connected to any grounding screw (if there is one) on the switch itself, as well as any grounding screw at the fixture (green wires that attach to the fixture are grounds). Now if using a plastic box, it is made of a material that is non conductive, however some plastic boxes have a metal strip inside that can still be used to connect equipment grounding wires, in the event that it does not use wire nuts to join the bare grounding wires together. The equipment grounding wire (bare in most cables) must be electrical conductively joined throughout the circuit. Green wires are also equipment grounding conductors.
At the 3 way switches (switch 1 & 3) there are 3 main electrical screws, one of these 3 screws is distinctly different in color (perhaps darker) than the other 2. This screw connection is called the common screw. It is very important that in order for all the switches to work as they are intended to that the correct wire is attached to the common screw. Basically as depicted in the drawings one switch has the ungrounded conductor (hot) from the circuit power supply cable attached to the common screw, where the other switch had the ungrounded conductor (hot) feed to the light fixture itself.
Please also note that there are a variety of manufactures out there that make 3 way switches so it is possible that the switch you buy may have the common screw located in a different spot or side of the switch then depicted in the drawings in this article, just make sure that the wire depicted to go to the common screw of each of the switches is actually connected to the common screw of the 3 way switch you bought. The other 2 wires going between the remaining screws of one switch to the other switch does not matter as long as one wire of the 2 remaining wires go on each of the remaining 2 screws of the switch.
At the 4 way switch (switch # 2) there are 2 sets of matching screws, one set will match in color and the other set will be distinctly different perhaps darker in color, it is important that the traveler wires from the previous switch are connected to one matching set, and the traveler wires going to the next switch are connected to a different matching set.
If there is an equipment grounding screw on the 3 way or 4 way switch it may be green in color and be separated away from the main connections of the switch and likely part of the metal frame that is also part of the mounting structure of the switch.
Extensions to this Switch circuit…
Be Aware that there is a limit by code on how many wires can be in a given size electrical box, when adding more wires to the same box you may have to install a larger and / or deeper box to allow space for more wires coming and out of the box.
Here is an article / explanation in regards to box fill calculations ‘Box Fill Calculation’
The instructions here are based on the fact that the circuit has already been wired to the configuration shown in this article and we are now making the wiring changes for onward power.
From the fixture location…
Only switched onward power is available from the fixture location.
Onward switched power…
(example more than one light fixture controlled by the same switches)
(showing bellow the fixture portion of the circuit)
Not shown in the diagram but the onward cable also has a bare wire (equipment grounding conductor) that also must be connected to all the other bare wires at the fixture electrical box.
Connection Instructions for onward cable (switched)
- a) Using an insulated wire nut, connect / join – the black wire from ‘switch 2 + the black wire connected to the switched ungrounded conductor (hot) of fixture+ the black wire of onward cable.
- b) Using an insulated wire nut, connect / join – the white wire from switch 2 + the white wire connected to the grounded conductor (neutral) of fixture + the white wire of onward cable.
Identification of wires in onward cable….
Black – Switched ungrounded conductor (hot – switched)
White – Grounded conductor (neutral)
From the switch locations….
Switch 1 options…
Only switched onward power available at the the switch 1 location.
Onward switched power…
Not shown in the diagram but the onward cable also has a bare wire (equipment grounding conductor) that also must be connected to all the other bare wires at the switch electrical box.
Connection Instructions for onward cable (switched)
- a) Using an insulated wire nut, connect / join – the black wire from switch 2 + the black wire of onward cable + the black wire connected to common screw of switch 1.
- b) Using an insulated wire nut, connect / join – the white wire coming from switch 2 + the white wire of onward cable.
Identification of wires in onward cable..
Black – Switched ungrounded conductor (hot – switched)
White – Grounded conductor (neutral)
Switch 2 options…
Only switched onward power available at the the switch 2 location.
Onward ‘Switched Power
Due to the number of wires at switch 2 have decided to not make a drawing but to give wiring instructions only
Not mentioned in instructions but the onward cable also has a bare wire (equipment grounding conductor) that also must be connected to all the other bare wires at the switch electrical box.
Connection Instructions for onward cable (switched)
- a) Using an insulated wire nut, connect / join – black wire from fixture + the black wire of onward cable + the black wire coming from switch 1.
- b) Using an insulated wire nut, connect / join – the white wire from fixture + the white wire coming from switch 3 + the white wire coming from switch 1 + the white wire of onward cable.
Identification of wires in onward cable….
Black – Switched ungrounded conductor (hot – switched)
White – Grounded conductor (neutral)
Switch 3 Options:
Only onward always on power is available from the switch 3 location
Onward always on power…
Not shown in the diagram but the onward cable also has a bare wire (equipment grounding conductor) that also must be connected to all the other bare wires at the switch electrical box.
Connection Instructions for onward cable (always on)
- a) Using an insulated wire nut, connect / join – the white wire from switch 2 + the white wire coming from the ‘circuit power supply cable’ + the white wire of onward cable.
- b) Using an insulated wire nut, connect / join – the black wire connected to the common screw of switch 3 + the black wire coming from ‘circuit power supply cable’ + the black wire of onward cable.
Identification of wires in onward cable….
Black – Ungrounded conductor (hot – always on)
White – Grounded conductor (neutral)
Foreign Users:
The colors of the wires depicted are based on the standards and code requirements / configuration in the United States and Canada. If you are viewing this site from a foreign country, your wiring standards and color of wires may be different but the principal and sequence of wiring will still remain the same. Therefore the information in this article may still be of use to you regardless of what country you may be in. Just translate the colors used here to the color of wires used in your country in regards to ungrounded (hot) conductors / grounded conductors (neutral) and equipment grounding conductors as well know applicable code requirements in your country.
WHILE EXTREME CARE HAS BEEN IMPLEMENTED IN THE PREPARATION OF THIS SELF-HELP DOCUMENT, THE AUTHOR AND/OR PROVIDERS OF THIS DOCUMENT ASSUMES NO RESPONSIBILITY FOR ERRORS OR OMISSIONS, NOR IS ANY LIABILITY ASSUMED FROM THE USE OF THE INFORMATION, CONTAINED IN THIS DOCUMENT, BY THE AUTHOR and / OR PROVIDER.
By: Donald Kerr